Medium Voltage Aerial Insulated Cable
-
Refined Matterial
-
Standard Process
-
Free Sample & Test
-
Long Life-circle
Product Details
Applications
The XLPE covered aluminum cable is constituted by a compact round conductor, composed by aluminum strands, blocked or not, and with a cross-linked polyethylene (XLPE) covered in black or gray color, with special characteristics to be resistant against electric tracking and UV-rays.
As XLPE is a thermoses material, it enables operation up to 90°C continuously implying in higher capacity when compared to the thermoplastic materials.
The main application for covered aluminum cables is on compact overhead, primary power distribution, medium-voltage networks located in urban and wooded areas. These cables are an excellent technical and economic option for companies all over the world, since they feature such advantages as low manufacturing cost and ease of installation.
Standard Specification
Covered Aluminum Cables -15kV
Cross section [mm²] |
No. of wires | Conductor diam. [mm] |
Overall Diameter [mm] |
Minimum breaking load [kgf] |
Approx. weight [kg/km] |
Max. DC-resistance at 20°C [Ohm/km] |
Ampacity 90°C [A] |
35 | 7 | 7.1 | 13.6 | 464 | 190 | 0.868 | 187 |
50 | 7 | 8.2 | 14.7 | 663 | 235 | 0.641 | 225 |
70 | 19 | 9.7 | 16.2 | 928 | 315 | 0.443 | 282 |
95 | 19 | 11.5 | 18 | 1259 | 400 | 0.320 | 345 |
120 | 19 | 12.9 | 19.4 | 1591 | 500 | 0.253 | 401 |
150 | 19 | 14.2 | 20.7 | 1988 | 580 | 0.206 | 456 |
185 | 37 | 16.2 | 22.6 | 2452 | 695 | 0.164 | 525 |
240 | 37 | 18.4 | 24.9 | 3182 | 875 | 0.125 | 625 |
300 | 37 | 20.7 | 27.1 | 3977 | 1070 | 0.100 | 721 |
Covered Aluminum Cables -25kV
Cross section [mm²] |
No. of wires | Conductor dia. [mm] |
Overall Diameter [mm] |
Minimum breaking load [kgf] |
Approx. weight [kg/km] |
Max. DC-resistance at 20°C [Ohm/km] |
Ampacity 90°C [A] |
35 | 7 | 7.1 | 15.7 | 464 | 235 | 0.868 | 186 |
50 | 7 | 8.2 | 16.8 | 663 | 305 | 0.641 | 224 |
70 | 19 | 9.7 | 18.3 | 928 | 370 | 0.443 | 280 |
95 | 19 | 11.5 | 20.1 | 1259 | 460 | 0.32 | 343 |
120 | 19 | 12.9 | 21.5 | 1591 | 560 | 0.253 | 397 |
150 | 19 | 14.2 | 22.8 | 1988 | 650 | 0.206 | 450 |
185 | 37 | 16.2 | 24.8 | 2452 | 770 | 0.164 | 519 |
240 | 37 | 18.4 | 27 | 3182 | 960 | 0.125 | 617 |
300 | 37 | 20.7 | 29.3 | 3977 | 1155 | 0.1 | 712 |
Covered Aluminum Cables -35kV
Cross section [mm²] |
No. of wires | Conductor dia. [mm] |
Overall Diameter [mm] |
Minimum breaking load [kgf] |
Approx. weight [kg/km] |
Max. DC-resistance at 20°C [Ohm/km] |
Ampacity 90°C [A] |
70 | 19 | 9.7 | 25.7 | 928 | 620 | 0.443 | 270 |
95 | 19 | 11.5 | 27.5 | 1259 | 732 | 0.32 | 329 |
120 | 19 | 12.9 | 28.9 | 1591 | 830 | 0.253 | 381 |
150 | 19 | 14.2 | 30.2 | 1988 | 937 | 0.206 | 432 |
185 | 37 | 16.2 | 32.2 | 2452 | 1083 | 0.164 | 497 |
240 | 37 | 18.4 | 34.4 | 3182 | 1290 | 0.125 | 589 |
300 | 37 | 20.7 | 36.7 | 3977 | 1502 | 0.1 | 674 |